Fire-Trol Columns (Square Type SH and RH) |
Fire-Trol Columns (Type SH
and RH)
WIDE FLANGE SHAPES - UL RATED |
| |
X106 - 2 Hour |
X104 - 3 Hour |
X101 - 4 Hour |
| WF size |
Shell Size |
Wt.
|
Shell Size |
Wt.
|
Shell
Size |
Wt.
|
| W4x13 |
6x6 |
28 |
7x7 |
37 |
8x8 |
45 |
| W5x16 |
7x7 |
37 |
8x8 |
45 |
9x9 |
61 |
| W6x15, 20, 25 |
8x8 |
45 |
8½x8½ |
41 |
9x9 |
61 |
| W8x18, 21, 24,
28, 31 |
10x10 |
72 |
10½x10½ |
59 |
11x11 |
67 |
| W8x35, 40, 48 |
10x10 |
72 |
10½x10½ |
59 |
11x11 |
67 |
| W8x58, 67 |
10½x10½ |
59 |
11x11 |
67 |
11½x11½ |
72 |
| W10x22 |
12x7½ |
51 |
12½x8 |
53 |
13x8½ |
61 |
| W10x26, 30 |
12x7½ |
51 |
12½x8 |
53 |
13x8½ |
61 |
| W10x33, 39 |
11½x9½ |
59 |
12x10 |
67 |
12½x10½ |
72 |
| W10x45 |
12x9½ |
63 |
12½x10 |
69 |
13x10½ |
75 |
| W10x49 |
11½x11½ |
72 |
12x12 |
87 |
12½x12½ |
83 |
| W10x54, 60, 68 |
12x12 |
87 |
12½x12½ |
83 |
13x13 |
89 |
| W10x77, 88 |
12½x12½ |
83 |
13x13 |
89 |
13½x13½ |
95 |
| W10x100, 112 |
13x13 |
89 |
13½x13½ |
95 |
14x14 |
102 |
| W12x26, 30, 35 |
14x8 |
63 |
14½x8½ |
69 |
15x9 |
74 |
| W12x40, 45 |
13½x9½ |
71 |
14x10 |
95 |
14½x10½ |
83 |
| W12x50 |
14x10 |
95 |
14½x10 |
78 |
15x10½ |
84 |
| W12x53 |
13½x11½ |
83 |
14x12 |
89 |
14½x12½ |
95 |
| W12x58 |
14x11½ |
85 |
14½x12 |
92 |
15x12½ |
98 |
| W12x65, 72, 79,
87 |
14x14 |
102 |
14½x14½ |
108 |
15x15 |
115 |
| W12x96 |
14½x14 |
108 |
15x15 |
115 |
15½x15½ |
122 |
| W12x120, 136 |
15x15 |
115 |
15½x15½ |
122 |
16x16 |
129 |
| W12x152, 170 |
15½x15½ |
122 |
16x16 |
129 |
16½x16½ |
136 |
| W12x190 |
16x16 |
129 |
16½x16½ |
136 |
17x17 |
144 |
Weight shown in
pounds per foot for shell and fireproofing only.
All shell sizes are shown in inches.
Information available upon request for sizes other than shown.
Refer to latest edition of A.I.S.C. steel construction manual for allowable safe loads.
|
|